Technical data
Performance characteristics
Pt100 accuracy class (EN 60751)
  • B (± 0.3 °C at 0 °C)
  • ± (0.3 + 0.005 × t)°C
  • A (± 0.15 °C at 0 °C)
  • ± (0.15 + 0.002 × t)°C
  • 1/3 B (± 0.1 °C at 0 °C)
  • ± 1/3 × (0.3 + 0.005 × t)°C
  • 1/6 B (± 0.05 °C at 0 °C)
  • ± 1/6 × (0.3 + 0.005 × t)°C
Process connection
Sensor tube material
  • AISI 316L (1.4404)
Ambient conditions
Degree of protection (EN 60529)
  • IP 67
Humidity
  • < 98 % RH , condensing
Output signal
Without transmitter
  • 1 x Pt100, 4-wire
With transmitter
  • 4 … 20 mA , 2-wire
  • 4 … 20 mA , 2-wire + HART®
Electrical connection
Cable
  • M16 plastic, cable dia. 5 ... 10 mm
  • M16 stainless steel, cable dia. 5 ... 9 mm
  • M20 plastic, cable dia. 8 ... 13 mm
  • M20 stainless steel, cable dia. 9 ... 13 mm
Compliance and approvals
EMC
  • EN 61326-1
Explosion protection
  • ATEX II 1 G Ex ia IIC T6...T4 Ga
  • ATEX II 3 G Ex ec IIC T5
  • Ex ia Simple apparatus, gas and dust
  • IECEx Ex ia IIC T6...T4 Ga

Software
Software

Downloads
Data sheet
Operating Manual
Certificates / approvals
Technical Reports / White Paper
3D CAD / CAE

Drawings
Drawings

Wall mounted version

(png | 100 KB)

Wall mounted version, cable sensor

(png | 218 KB)

Wall mounted version, fixed sensor

(png | 189 KB)

Pipe mounted version

(png | 260 KB)

Pipe mounted version, cable sensor

(png | 229 KB)

Accessories
Programming tool
Accessories process sensors – FlexProgrammer 9701 FlexProgrammer 9701
Configuration tool for process sensors

Article no.: 10260076

  • Operated from a PC, supplied from the USB port
  • Remote operation, supplied from a battery
  • User-friendly software with help menus
  • CleverLevel LFFS / LBFH / LBFI / LBFS / LBFS hanging / PL20, CombiLevel PLP70, CombiPress PFMH / PFMN, CombiTemp TFRH / TFRN, CombiLyz AFI4 / AFI5, CombiView DFON, PBMH, PBMH autoclavable, PBMN flush, PBMN low pressure, PBMN high pressure, PBSN, PP20S, FlexTop 22xx, FlexTemp 23xx, TCR6, TE2, TER8, PT20, TFR5
Accessories
Accessories process sensors – ZEX-ALL.B28RD100 ZEX-ALL.B28RD100
Dual-channel safety barrier (with diode return channel)

Article no.: 11217062

  • Applicable for all Baumer Ex i 4 … 20 mA current loop sensors and Ex i LBFH/LBFI level switches
  • DIN rail mounted
  • HART compatible
  • Earthed field circuit
Accessories process sensors – ZEX-ALL.B30RS075 ZEX-ALL.B30RS075
Single-Channel safety barrier (for potential-free contacts)

Article no.: 11217063

  • Applicable for Baumer DFON relay outputs
  • DIN rail mounted
  • Earthed field circuit
2909

  • R 1/2 ISO 7-1
  • AISI 316L (1.4404)


To the top